Tecto RF WSC2 - Sets for cooling applicatons

Refrigeration units in split design for storing fruits and vegetables, packaged food and packaged meat enable an uncomplicated handling even with large amounts of waste heat. By separating the evaporator and condensing unit, a wide range of installation options can be implemented on the inside and outside walls of a building.

Key benefits

  • Reliability through high operational safety
  • Use of components from well-known manufacturers
  • Cost-optimised operations due to easy installation and high energy efficiency
  • Rapid availability due to pre-assembled, coordinated components
  • Sets for all different kinds of cooling applications

For availability of the split refrigeration units, please contact the local sales company in your country. 


WSC2

1800 PF

WSC2

2200 PF

WSC2

2800 PF

WSC2

4100 PF

WSC2

5500 PF

Cooling capacity 

[W]¹

1800/1600

2200/1900

2800/2300

4100/3400

5500/4600

Room volume up to [m³]²

30

40

55

90

130

Cold room temperature adjustment

range [°C]

+5 to +20

+5 to +20

+5 to +20

+5 to +20

+5 to +20

Allowed ambient 

temperature [°C] ³

-15 to +43

-15 to +43

-15 to +43

-15 to +43

-15 to +43

Refrigerant / GWP 

R513A/573

R513A/573

R513A/573

R513A/573

R513A/573

Sound pressure level day/night [dB(A)] ⁴

34/34

34/34

39/36

40/37

40/37

Voltage / Phases / 

Frequency (V/-/Hz)

230/1/ 50

230/1/ 50

400/3/50

400/3/50

400/3/50

Defrosting type

Circulating air

Circulating air

Circulating 

air

Circulating 

air

Circulating 

air

Dimensions condensing 

unit HxWxD [mm]

600x900x350

600x900x350

840x1030x425

840x1030x425

840x1030x425

Dimensions evaporator

HxWxD [mm]

455x752x430

455x752x430

455x752x430

455x1212x430

455x1212x430

¹ Condensing unit; evaporation temperature t₀ -5°C, ambient temperature + 32°C / 43°C; evaporator superheat 10K; influences of installation location and other refrigeration circuit components must be considered independently

² Basis of calculation for room size: room temperature +5°C, ambient temperature +25°C, heat extraction from goods 15 K, operating time 16 h/day, goods handling 1/7 per day, inspection and lighting 0.5 h / day

³ Max. compressor inlet superheat 20K

⁴ Based on AR5 / IPCC

⁵ Condensing unit, A-weighted equivalent sound pressure level at a distance of 10m


WSC2

1700 PM

WSC2

2100 PM

WSC2

2600  PM

WSC2

3700 PM

WSC2

5100 PM

WSC2 6400 PM

Cooling capacity 

[W]¹

1700/1400

2100/1800

2600/2100

3700/3100

5100/4300

6400/5400

Room volume up to

[m³]²

25

35

45

70

105

140

Cold room tempe-

rature adjustment

 range [°C]

+2 to +20

+2 to +20

+2 to +20

+2 to +20

+2 to +20

+2 to +20

Allowed ambient

 temperature [° C] ³

-15 to +43

-15 to +43

-15 to +43

-15 to +43

-15 to +43

-15 to +43

Refrigerant / GWP 

R513A/573

R513A/573

R513A/573

R513A/573

R513A/573

R513A/573

Sound pressure level 

day / night [dB(A)] 

34/34

34/34

39/36

40/37

40/37

41/38

Voltage / Phases / 

Frequency (V/-/Hz)

230/1/50

230/1/50

400/3/50

400/3/50

400/3/50

400/3/50

Defrosting type

Electrical

Electrical

Electrical

Electrical

Electrical

Electrical

Dimensions condensing 

unit HxWxD [mm]

600x900x350

600x900x350

840x1030x425

840x1030x425

840x1030x425

1245x1030x425

Dimensions evaporator

HxWxD [mm]

455x752x430

455x752x430

455x752x430

455x1212x430

455x1212x430

455x1672x430

¹ Condensing unit, Evaporation temperature t₀ -7°C; ambient temperature + 32°C / 43°C; evaporator superheat 10K; influences of installation location and other refrigeration circuit components must be considered independently

² Basis of calculation for room size: Room temperature +2°C, Ambient temperature +25°C, heat extraction from goods 15K, operating time 16 h/day, goods handling 1/7 per day, inspection and lighting 0.5 h / day

³ Max. Compressor inlet superheat 20K

⁴ Based on AR5 / IPCC

⁵ Condensing unit, A-weighted equivalent sound pressure level at a distance of 10m


WSC2

2100 FV

WSC2

2700 FV

WSC2

3400 FV

WSC2

5000 FV

WSC2

6700 FV

Cooling capacity 

[W]¹

2100/1800

2700/2300

3400/2800

5000/4200

6700/5700

Room volume up to [m³]²

35

50

65

105

150

Cold room temperature adjustment

range [°C]

+5 to +20

+5 to +20

+5 to +20

+5 to +20

+5 to +20

Allowed ambient tem-perature [°C] ³

-15 to +43

-15 to +43

-15 to +43

-15 to +43

-15 to +43

Refrigerant / GWP 

R513A/573

R513A/573

R513A/573

R513A/573

R513A/573

Sound pressure level day / night [dB(A)] 

34/34

34/34

39/36

40/37

40/37

Voltage / Phases / 

Frequency (V/-/Hz)

230/1/50

230/1/50

400/3/50

400/3/50

400/3/50

Defrosting type

Circulating air

Circulating air

Circulating 

air

Circulating 

air

Circulating 

air

Dimensions condensing 

unit HxWxD [mm]

600x900x350

600x900x350

840x1030x425

840x1030x425

840x1030x425

Dimensions evaporator

HxWxD [mm]

455x752x430

455x752x430

455x1212x430

455x1212x430

455x1672x430

¹ Condensing unit, Evaporation temperature t₀ 0°C; ambient temperature + 32°C / 43°C; evaporator superheat 10K; influences of installation location and other refrigeration circuit components must be considered independently

² Basis of calculation for room size: Room temperature +8°C, Ambient temperature +25°C, heat extraction from goods 15K, operating time 16 h/day, goods handling 1/7 per day, inspection and lighting 0.5 h / day

³ Max. Compressor inlet superheat 20K

⁴ Based on AR5 / IPCC

⁵ Condensing unit, A-weighted equivalent sound pressure level at a distance of 10m